General
L-ION series products are universal configurable controllers that can be used to manage a variety of building systems including heating, ventilation, air-conditioning (HVAC) systems. Advanced control strategies are available for optimized performance. All functions are configurable via series of parameters. A comprehensive set of templates assure easy start-up.
Inputs
Analog inputs are optimized for PT1000 type temperature sensors and 0-10 VDC devices. 13 bit A/D converters assure high resolution measurements. All inputs are software configurable.
Digital inputs allow freeze protection, emergency stop and fire scenarios to be implemented. Additional information such as filter clogging may also be communicated to the BMS via the Modbus protocol.
Potentiometer input
On the -EP models, one dedicated input allows a remote potentiometer (1-11 kOhm) to be used for remote set-point adjustment.
Outputs
Analog outputs are used to control valve and damper actuators, humidifiers, frequency drives, etc.. -EF models drive 24 VAC 3-point actuators. -EP models have 0/2-10 VDC outputs
Configuration
L-ION's may be configured to control a wide range of systems. The configurations are saved in non-volatile memory, thus pre-configuration is possible prior to shipment.
Four control loops are provided to control four different process variables. For example, temperature and humidity can be controlled on an air handling unit, or four valves may be controlled on four heat-exchangers.
In addition to basic proportional + integral (PI) control, upper and lower limits, compensation, cascade control can be configured for each loop. Sequential control of heating and cooling systems is possible.
All the parameters are set using the buttons and display on the controller. Instead of setting all the parameters from scratch, templates are available for a wide range of common systems. Predefined settings may then be optimized for the applied system.
Time schedules
-M models have time schedules that allow the system to be operated on desired periods. Weekly programming is possible.
Communication
-M models also offer Modbus RTU protocol over RS485 is provided to communicate with Building Management Systems. This allows manufacturers of AHU's and similar equpment to ship BMS ready devices.
Log records
Troubleshooting is facilitated by the logs of fault and alarm conditions, power failures and manual overrides.
Specifications
Model | L-ION EF21 | L-ION EF33 | L-ION EP33 | L-ION EP44-M | |
General | 8 bit microcontroller, 13-bit A/D converter EEPROM memory, LCD with back-light |
||||
Nominal voltage Power consumption |
24 V AC +%10-%15, 50/60Hz 3 VA |
||||
Analog Inputs | 2 ea | 3 ea | 3 ea | 4 ea | |
0(2)-10 Vdc 0(4)-20 mA (500 Ohm resistor required) PT1000 temperature sensor |
|||||
Digital inputs (Voltage-free contact) |
2 ea | 7 ea | |||
Potentiometer input | - | 1 ea, 11kOhm | |||
Analog Outputs | 1 ea | 3 ea | 3 ea | 4 ea | |
24 VAC 3-point | 0-10 Vdc / 2 mA | ||||
Digital outputs | - | 3 ea SPST 5A |
|||
Communication | - | Modbus RTU | |||
Ambient temperature range Non-operating range Humidity range |
0..50 °C -25..+75 °C %5...95 rh, non-condensing |
||||
Weight Dimensions Mounting |
380 gr (Gross 450 gr) 157 x 86 x 60 For 35 mm DIN rail mounting |
||||
Degree of protection | IP20, EN 60529 | ||||
Connections | Plug-in, max 1 x 2.5 mm² |